Correct as required d motor overloads tripped.
Power flame burner troubleshooting.
Other flame sensors are available to comply with specifications or codes.
All power flame burners are operationally fire tested at the factory.
Claims of shortage or damage must be immediately filled with the carrier.
Capacities specifications dimensions ja1 rpt 0813 rev 0813 a.
Defective on off or fuel transfer switch.
By using power flame factory service professionals you are putting the ones that build the burners along side you from start up to commissioning.
Control circuit has an open control contact.
Gas oil or gas oil burner general 1.
We help with troubleshooting and training or scheduling an on site visit from one of our service professionals.
On some oem boiler applicatons a 1 2 hp motor is required.
Components not mounted on the burner shipped loose are designated with an l on the sheets.
Burner fails to start a.
If a flame signal is detected verify the flame retention tab and ignition electrode are properly positioned per figure 11.
At the end of the pilot trial for ignition and blower purge period the flame safeguard control should shut the system down in a safety lock out mode requiring manual reset of the flame safeguard control to restart burner.
Power flame service is a phone call away and gives immediate access to assistance over the phone.
Click here for the power flame customer support.
Uncrate burner carefully and check all parts received sheets supplied by power flame.
We manufacture a wide range of commercial burners industrial burners boiler burners.
Check limits low water cutoff proof of closure switch and others as applicable.